技术文章

西门子接口模块6ES7155-6AU01-0CN0

点击次数:91 发布时间:2021/11/22 10:28:43
 西门子接口模块6ES7155-6AU01-0CN0

SIMATIC ET 200SP,PROFINET, 2 接口,接口模块 IM 155-6PN/2 高性能, 1 个插接位置,用于总线适配器, 蕞多 64 个 I/O 模块 和 16 ET 200AL 模块, S2 冗余,多功能热插拔, 0.25ms,同步模式, 可选的 PN 电缆夹, 包括服务器模块

  6ES7155-6BA01-0CN0SIMATIC ET 200SP, PROFIBUS bundle IM, IM 155-6DP HF, max. 32 I/O modules and 16 ET 200AL modules, Multi-hotswap, bundle consists of: Interface module (6ES7155-6BU01-0CN0), Server module (6ES7193-6PA00-0AA0), PROFIBUS connector (6ES7972-0BB70-0XA0)  6ES7158-0AD01-0XA0SIMATIC DP, DP/DP 耦合器 耦合模块,用于连接 两个 PROFIBUS-DP 网络 冗余电流馈电  6ES7155-6AU30-0CN0SIMATIC ET 200SP,PROFINET, 三端口接口模块, IM 155-6PN/3 高性能, 2 个插槽,用于Busadapter, 蕞多 64 个 I/O 模块 和 16 ET 200AL 模块, S2 冗余,多功能热插拔, 0.25ms,同步模式, 可选的 PN 电缆夹, 包括服务器模块

河南兆阳自动化科技有限公司销售西门子千万余产品 尽新老顾客您来询价订货采购,欢迎您来兆阳公司,谢谢您的光临! 
连系人  :邵经理
电   :191+ 39 98+ 27 30        同微号

产品
商品编号(市售编号) 6ES7155-6AU01-0CN0
产品说明 SIMATIC ET 200SP,PROFINET, 2 接口,接口模块 IM 155-6PN/2 高性能, 1 个插接位置,用于总线适配器, 蕞多 64 个 I/O 模块 和 16 ET 200AL 模块, S2 冗余,多功能热插拔, 0.25ms,同步模式, 可选的 PN 电缆夹, 包括服务器模块
产品家族 Interface modules and BusAdapter
产品生命周期 (PLM) PM300:有效产品
价格数据
价格组 / 总部价格组 IR / 255
列表价(不含税) 显示价格
您的单价(不含税) 显示价格
金属系数
交付信息
出口管制规定 AL : N / ECCN : EAR99H
工厂生产时间 170 天
净重 (Kg) 0.170 Kg
包装尺寸 10.60 x 12.80 x 6.80
包装尺寸单位的测量 CM
数量单位 1 件
包装数量 1
其他产品信息
EAN 4047623409755
UPC 804766765933
商品代码 85176200
LKZ_FDB/ CatalogID ST76
产品组 4520
组代码 R151
原产地 德国

西门子接口模块6ES7155-6AU01-0CN0

概述

PROFINET IM 155‑6PN High Feature interface module, with reference ID label

PROFINET Interface Module IM 155-6PN/2 High Feature
  • Interface module for connecting the ET 200SP station to PROFINET IO
  • 24 V DC supply for interface module and backplane bus
  • Integrated 2-port switch for line configuration
  • Handling of complete data transfer with the controller
  • Data exchange with the I/O modules via the backplane bus
  • Support of identification data I&M0 to I&M3
  • Delivery including server module
  • BusAdapter with integrated 2-port switch for individual selection of the PROFINET IO connection system can be ordered separately
PROFIBUS IM 155‑6DP High Feature interface module
  • Max. 32 I/O modules, also PROFIsafe modules with complete diagnostic support
  • Max. 244 bytes in each case for input and output data per module and per station
  • Data update time: Typ. 5 ms
  • PROFIBUS connection via 9-pin sub‑D socket
  • Bundle including server module and PROFIBUS plug

BusAdapter BA 2×RJ45

BusAdapter (BA)

A BusAdapter can be used to adapt the universal PROFINET IO interface of the interface module to the specific requirements of the environment of use. If a connection socket is faulty or when changing the connection system at a later stage, it is only necessary to replace the BusAdapter.

The following BusAdapters are available:

  • BA 2×RJ45 
    With two sockets for commercially available RJ45 plugs; suitable for standard applications with moderate mechanical strength and EMI resistance
  • BA 2×FC 
    With two FastConnect terminals for direct connection of the bus cables; suitable for applications with higher mechanical strength and/or EMI resistance (5x higher resistance against vibrations and EMI)
  • BA 2×SCRJ 
    With two optical PROFINET interfaces for connection of optical-fiber cables via SC RJ plug-in connectors (5x higher resistance against vibrations and EMI; PROFINET cable lengths between two stations up to 300 m)
  • BA 2×LC 
    With two optical PROFINET interfaces for connecting fiber-optic cables LC multimode glass-fiber
  • BA LC/RJ45 
    With two PROFINET interfaces:
    • 1 × optical, for connection of fiber-optic cables via LC multimode fiber-optic cable (port 1)
    • 1 × electrical, for connection of bus cable with standard RJ45 plug (port 2)
  • BA LC/FC 
    With two PROFINET interfaces:
    • 1 × optical, for connection of fiber-optic cables via LC multimode fiber-optic cable (port 1)
    • 1 × electrical, for direct connection of FastConnect bus cable (port 2)
  • BA SCRJ/RJ45 
    With two PROFINET interfaces:
    • 1 × optical, for connection of fiber-optic cables via SC RJ connectors (port 1)
    • 1 × electrical, for connection of bus cable with standard RJ45 plug (port 2)
  • BA SCRJ/FC 
    With two PROFINET interfaces (5x higher resistance against vibrations and EMI):
    • 1 × optical, for connection of fiber-optic cables via SC RJ connectors (port 1)
    • 1 × electrical, for direct connection of FastConnect bus cable (port 2)
设计

The IM 155-6PN/2 High Feature interface module is snapped directly onto the DIN rail.

Device features:

  • Diagnostics displays for errors (ERROR), Maintenance (MAINT), operation (RUN) and power supply (PWR) as well as one link LED per port
  • Optional inscription with labeling strips (light gray), available as:
    • Roll for thermal transfer continuous feed printer with 500 strips each
    • Paper sheets for laser printer, A4 format, with 100 strips each
  • Optional equipping with a reference ID label

The selected BusAdapter is simply plugged onto the interface module and secured with a screw. It can be equipped with a reference ID label.

 