产品展示
优质供应
详细内容
generic ascii ethernet communications interface module
mvi56-gec
the mvi56-gec module is a single-slot, backplane compatible solution for the allen-bradley controllogix platform. this module provides communication between ascii devices using the tcp/ip protocol and the processor.
compatible devices may be either ascii instruments with ethernet built in or ethernet connection via a thin server to the existing serial (rs-232/422/485) ascii device. five servers are present on the module permitting both the reception and transmission of data between the allen-bradley processor and attached devices. this module is designed by prosoft technology and incorporates licensed technology from allen-bradley (controllogix backplane technology).
features
- five servers to receive and/or transmit data
- 10/100mb ethernet-compatible interface
configurable parameters
- service port number
- connection timeout
- close type
- simple ladder logic operation
- setup and monitoring through rs-logix 5000 software and user-constructed configuration file (gec.cfg)
- controllogix backplane interface via i/o access
applications
the use of the tcp/ip protocol with ethernet at the device level on the plant floor is becoming widespread in many industry segments. using the mvi56-gec the advantage of ethernet speed is realized while allowing greater distances between networked devices.
- bar code scanner interfaces
- weigh scale interfaces
- legacy ascii protocol connections
- terminal port emulation
- printer driver (alarm/status printer)
functional specifications
functional specification for this module are as follows:
communication parameters
- 57600, no parity, 1 stop (fixed), 8 data bits
configuration/debug port (cfg)
- module configuration
- communication and backplane transfer stats
- server statistics and configuration
- warm boot
- configuration file upload/download
- network configuration (includes the module ip address, mask, gateway address)
each server monitors
- state
- ip and port number of connected client
- number of messages received and transmitted
- error codes
- ascii character strings up to 2048 characters in length supported
- full hardware handshaking control, providing radio, modem, and multi-dr-opsupport
- memory usage is completely user-configurable, supporting the storage and transfer of up to 4000 bytes to/from the control processor
module error and status conditions returned to processor for diagnostic purposes
- module status
- port error status word (bit mapped)
- port receive state
- port receive character count
- port receive block count
- port transmit state
- port transmit character count
- port transmit block count
- all data related to the module is contained in a single controller tag with defined ob-jects to ease in the configuration, monitoring, and interfacing with the module
- module configuration and communication configuration data is transferred to the mvi56-gec via a pre-defined user data type in the processor
hardware specifications
- ethernet port- 10/100m- 10base-t connector- link and activity led indicators
- form factor:- single slot - 1756 chassis compatible- local or remote rack
- backplane current load: 800 ma @ 5 v
- operating temperature: 0 to 60 deg c (32 to 140 deg f)
- storage temperature: -40 to 85 deg c (-40 to 185 deg f)
- shock:- 30g operational- 50g non-operational
- vibration: 5 g from 10 - 150 hz
- relative humidity: 5-95% (w/o condensation)
- led indicators:- module status- backplane transfer status- application status- serial activity and error led status
- configuration serial port (prt1):- db-9m pc compatible- rs-232 only- hardware handshaking
ordering information
part number | part desc-ription |
mvi56-gec | generic ascii ethernet communications interface module |