modbus communications interface module
mvi94-mcm-std
the mvi94-mcm flex i/o module allows the user to easily add a modbus port to a flex based i/o system.
the mvi94-mcm modbus master solution consumes a single flex i/o slot, and via flex backplane communications can be interfaced to the currently available flex communication adapters. the mvi94-mcm solution enables the many field instruments and other modbus slave compatible devices to be integrated into the rockwell automation flex environment.
features
the mvi94-mcm module has two serial ports
prt1 -- debug/configuration port rs-232
prt2 -- modbus port rs-232/422/485
applications
the mvi94-mcm module is the ideal solution for many applications where modbus master/slave connectivity needs to be added to a flex system. the mvi94-mcm module can be found in many industrial sectors and in following applications -
- foreign device data concentrator
- pipelines & offshore platforms
- food processing
- mining
- pulp & paper
functional specifications
the mvi94 unit can sit in any flex rack i/o slot position and works with all currently available flex communication adapters.
debug/configuration port (prt1)
communication parameters
- baud: 57,600 (fixed)
- parity: (fixed)
- stop: 1 (fixed)
port functionality
- configuration of module
- comm and backplane transfer stats
- protocol data monitor
- internal database viewer
modbus master port (prt2)
- rtu mode (binary) with crc-16 and ascii mode with lrc error checking
- memory usage is user configurable
- full radio, modem and multi-dr-op support
- support for the storage and transfer of up to 3996 registers to/from the control processor
- 125 word read and write command lengths supported
- floating point data movement supported
software configurable communication parameters
- parity: , odd or even
- stop bits: 1 or 2
- baud rate: 110 to 115,200 baud
- rts on delay: 0 to 65535 ms
- rts off delay: 0 to 65535 ms
protocol specifications - modbus master port
binary and register data read and write function codes are supported
1 coil read
2 input read
3 multiple register read
4 input register read
5 coil write
6 register write
15 multiple bit write
16 multiple register write
- up to 100 entries in the command list, each fully configurable for function, register to/from addressing and word/bit count/word and byte swap
- conditional and continuous command list polling
- event driven bit and register write commands
- communication error codes returned to ladder logic on a per command basis
- configuration possible via ladder logic or by simple file text file download to configuration/debug port.
hardware specifications
- application serial ports (prt1, prt2)- application port to db-9m pc compatible connector is supplied- rs232/422/485 jumper se-lectable- rs232 handshaking configurable- 500v optical isolation from backplane
- form factor- single slot - 94 backplane compatible- locate in any slot of backplane
- dimensions- 46 mm x 94 mm x 75 mm- 1.8 in x 3.7 in x 2.95 in- weight 200 g (approximately
- backplane current load- 20 ma @ 5 v
- external power supply- 12-24vdc- 340 ma to 170 ma
- operating temperature- 0 to 55 deg c (32 to 140 deg f)
- storage temperature- from -40 to 85 deg c (-40 to 185 deg f)
- shock- 30g operational- 50g non-operational- 5 g from 10 - 150 hz
- relative humidity- 5-95% (w/o condensation)
- led indicators- module status- backplane transfer status- application status- serial activity and error led status
- configuration serial port (prt1)- db-9m pc compatible- rs-232- hardware handshaking
- application serial port (prt2)- db-9m pc compatible- rs232/422/485 jumper se-lectable- 500v optical isolation from backplane
ordering information
part number | part desc-ription |
mvi94-mcm-std | modbus communications interface module |