Intelligent Channels Measurement Instrument

点击次数:319 发布时间:2012/12/13 15:38:56

Normal07.8 磅02falsefalsefalseMicrosoftInternetExplorer4

1. Summary

YK-19 series intelligent Channels Measurement instrument is intelligent, high accuracy controller for temperature, pressure or level measurement. When use it to equipped with temperature, pressure or level sensor, we can consist temperature, pressure or level measurement control system for various type and range. provide RS232 or RS485 to communication with computer or PLCThe instrument has a real-time clock for user get date and time

2.Technical specifications

Input signal: Resistance temperature Detector  Pt100, Cu50, Cu100,3 wires conncet

Measurement accuracy :  0.2FS±1 digit

Alarm Output: buzzer

communication: isolation  RS485, baud 12009600bps

transmit: isolation 4-20mA for the first channel,<250Ω

Display : double 4 digit LED display.

Power suply:  220VAC.

Power consumption:  2W

Temperature :  050

Ambient humidity:  <85RH

Front panel dimension : 160mm×80mm

Installation dimension : 152mm×76mm

Normal07.8 磅02falsefalsefalseMicrosoftInternetExplorer4

3. Operation

Key-press Description

Press the KEY to mute the Buzzer.

at setting parameters state, press the key return to work state. At work state, press the key to switch cycle display and static display. While at cycle display state,the bottom LED are display –xx-, at static display state, the bottom LED are display xx

EnPress the SET key to enter setting status.After chang the current parameter and press the key to enter the next parameter.

at setting parameters state, press key making parameter increase one. and hold the key, value will increase or decrease quickly and release for stop. At static display state, press key will change to next channels value display.

at setting parameters state, press key making parameter decrease one. and hold the key, value wil decrease quickly and release for stop. At static display state, press the key will change to next channels value display.

After power on the display window displays HELO to indicate self-checking is right, displays -HH- indicates input over range or sensor disconnection or short-circuit. Instrument adopts man to machine talk model for input parameter, and use various prompting to indicate what kind of data should input. At the work state, the up LED display measured value, the bottom LED display the number of the corresponding channel.The last two are the date(-Ht-) and time(-Lt-).

(1)press the En key, the up display window displays –Cd-,bottom LED will display 800, Only 800 is changed to 808, and then press En key again will make the instrument to access the setup parameter setting status, other value is denied for preventing field operators from set parameters incorrectly by mistake.     

(2) -LP-: the instrument measuring the number of channels,rang:1~16, Factory default 10.

(3)1-Snthe first channel intput sensor type, Reference the table below, Factory default P100.

intput sensor type table

Para Prompt

sensor type

Para Prompt

sensor type

  P100

  Pt100         

  tc-t

  T

  C100

  Cu100

  tc-n

  N

  Cu50

  Cu50

  tc-J

  J

  bA1

 BA1

  4-20

  4-20mA

  bA2

  bA2

  0-10

  0-10mA

  tc-s

  S

  0-20

  0-20mA

  tc-k

  K

  1-5U

  1-5V

  tc-e

  E

  0-5U

  0-5V

  tc-b

  B

  0-50

  0-50mV

(4)1-nd:the 1st channel measured value’s decimal point position. Rang 0-3, Factory default 1.

(5)1-PL: the 1st channel lower range value, only for the first,it is lower range value for the transmitter output too.

(6)1-PH: the 1st channel higher range value, only for the first,it is higher range value for the transmitter output too. For example,1-PL=0.0,1-PH=300.0, first channel measured value is150.0,then the output 4-20mA value is 12.0mA.

(7)2-Snthe 2nc channel intput sensor type.

……

(8)1-HA: the 1st channel ultra-high alarm value.

(9)1-LA: the 1st channel ultra-low alarm value.

……

(10)1-Eo: the 1st channel measured value deviation rectify.ex: actual the 1st value is 30.0, currently display value is 29.2,then the parameter 1-Eo=0.8. Factory default 0.0

(11)2-Eo: the 2nd channel measured value deviation rectify.

……

(12)Addr:the communication address for computer, rang 0199Factory default 1

(13)baud:the communication baud for computer, 1200240048009600 four items for choiceFactory default 9600.

(14)-Ht-: Current clock date, rang 1.01~12.31.

(15)-Lt-: Current clock time, rang 0:00~23.59.

(16)tSthe cycle display interval, unit second, rang 1~9999, Factory default 5

After parameter sets are finished, LED will display End and then go to working status.

Normal07.8 磅02falsefalsefalseMicrosoftInternetExplorer4

4. Communication specifications

The instrument has RS485 interface, direct communication with the computer. RS485 standard communication distance 1.5km, Can be connected to multiple devices/ instrument.Data character format is 1 initial bit , 8 data bits, 1 stop bit, no parity bit.

The instrument using modbus-rtu standard communication protocols,using 3x or 4x. Register addres from 1 to 18.

 

4x001               1 ch value 

4x002              2 ch value

……

4x016               16 ch value

4x017               clock date

4x018               clock time

EXthe parameter Addr=1,the 1 channel value=100.0

host send query message: 01 03 00 00 00 01 84 0A.

Instrument return data: 01 03 02 03 E8 B8 FA.(0x03e8=1000)

Host send

Addr

function

Starting Address high

Starting Address low

No. of Points Hi

No. of Points Lo

 

CRC16 high

CRC16

low

01

03

00

00

00

01

84

0A

Instrument return

Addr

function

Byte Count

Data High

Data low

 

CRC16 high

CRC16

low

01

03

02

03

E8

B8

FA

 

 

原创作者:北京宇科泰吉电子有限公司