您的位置:首页 > 技术文献 > 技术交流 > 冷水机安装的注意事项
一、 安装注意事项
Installation Notices
1、冷却水塔吨数不得低于冷冻机吨数,且需考滤安全系统,故要大于冷冻机吨数的30%
如冷冻机为10RT,冷却水塔须为15RT……经此类推。
Tunnage of cooling water tower should be more than that of the chiller by 30% considering the security system.
For example, if the tunnage of the chiller is 10RT, then the cooling water tower should be 15RT…and the like.
2、冷却水塔之水管径不得小于冷冻机之出口管径。管径大小可参考规格表。
The diameter of the cooling water tower pipe should be larger than the outlet pipe of the chiller. Refer to the size listed in specification.
3、冷却水塔须安装在室外通风良好之场所,且距离冷冻机不得远于
如冷冻机为10RT,冷却水出入口径为1-1/2",若距离冷却水塔为
The cooling water tower should be installed in outdoor place with good ventilation, and the distance from the chiller should be within 20 meters. If it is over
For example, the chiller is 10RT, cooling water inlet and outlet caliber is 1-1/2", if the distance from cooling water tower is 30 meters, then the pipe diameter should be 2".
4、冰水系统管路不得高于冷冻机的冰水出入口,否则停机后水箱会溢水。(请于冰水出口加装逆止阀)
Ice water system pipeline should be lower than that of the chiller’s inlet and outlet, otherwise water will overflow from the tank after shutting down the machine (please install check valves in the ice water outlet).
5、冷冻机安装处不得完全靠墙壁,须距离50公分以上,以利保养维修。
The chiller should not be installed alongside the wall. It must be away from the wall by more than 50 centimeters for maintenance.
6、气冷式冷冻机须放置在空气流通、粉尘少的地方。
Air-cooling chiller should be deposited in a place with good ventilation and less dust.
7、外主电源线不得小于冷冻主电源电线,其它电源开关不得小于冷冻内之无熔丝开关世界安全倍数,亦不得大于50%。
For the no-fuse breaker’s world safety multiple, the outside main power supply wire should be higher than the freezing main wire, and other power supply switch should be higher than freezing inside switch but should not be more than 50%.
※ 水冷式冷冻机简易安装图
※ Simple installation plot of water-cooling chiller
二、开机注意事项 Startup Notices
1、电源系统: Power supply system:
(1).将本机电源线之地线接地(黄绿色线)或从机殻螺丝钉接地。
Earth the ground wire (yellow-green wire) of the machine or earth it by the screw of the shell.
(2).检查电源、电压及电流容量是否符合本机使用 3∮380V50Hz之电源,无熔丝开关(NFB)。
Check if the capacity of the power supply, voltage and current is suitable for this machine to use 3∮380V50Hz power supply and no-fuse breaker.
(3).将本机电源线接至铭牌上所定之电源。
Connect the power supply wire of this machine to the power supply specified by nameplate.
2、冷却系统:Cooling System:
(1) .冷却水塔是否运转,抽水泵浦转向是否正确,进出水口是否接对。
Check if the cooling water tower works and if the water pumping direction is right, whether the inlet and outlet connect correctly.
(2) .冷却循环水,压力应在
The pressure of circulating cooling water should be
(3). 冷却水温,不可超过
The temperature of cooling water should not be higher than
(4).打开本机冷却水出入口球阀,自动补水至水箱(如补充水无法进入水箱,即冷却水压力不够)。
Turn on the ball valve of the cooling water’s inlet and outlet, supplement water automatically (if fail, the pressure of the cooling water is not enough).
※ 如贵公司所订冷冻机为冰水系统(如用纯水)与冷却水系统水质不同,请自行添加至水箱。
※ If the chiller ordered by your company requires different quality of water (like pure water), please add it to the water tank by yourself.
※ 如贵公司所订冷冻机的冰水槽移至外部加大,须先把冰水槽加满水位。
※ If the chiller ordered by your company needs to move the ice water tank to the outside and enlarge it, you shall fill the tank with water to the water line.
※ 如贵公司所订冷冻机为气冷式,则不用冷却水塔,只须从后本机补给水球阀补水。
※ If the chiller ordered by your company is air-cooling, then cooling water tower is not needed, just supplement water through the ball valve.
3、检查冰水进出口是否接对。
Check if the inlet and outlet of ice water is connected right.
4、以上事项正确后,方可开机。
Make sure the above items are all right, and then turn the machine on.
5、本机系统注意事项:
Attentions:
(1) .温度勿设定
The temperature should not be below
(2).温度如设定
If the temperature is below
tank.
(3).本机设有电源相位识别,保护马达,泵浦反转及故障指示电路,如有任何故障将无法启开马达及压缩机。
This machine has power supply phase recognition, motor protection,
pump reversal and malfunction indicator circuit, so the motor and
compressor will not function if there is any fault.
(3) .冻结指示灯亮,压缩机无法启动,泵正常运转。
When the freezing indicator light is on, the compressor will not function but the pump still works.
三、保养注意事项 Maintenance Notices
1、 定期检查冷媒量,运行中指示低压应在
Check the cooling medium quantity regularly, the low pressure should be above
2、 若为半封闭式压缩机,要定期检查油量,正常应在窗口的2/3以上。
If the compressor is semi-closed, check the oil quantity regularly and it should be more than 2/3 of the window normally.
3、 每隔六个月刷洗冷凝管一次。
Clean the condenser every 6 months.
4、 每隔三个月清洗冷却水塔一次。
Clean the cooling water tower every 3 months.
5、 冷却水质不良,请加装Y型过滤器。
Install Y-type filter if the quality of cooling water is not good.
6、 请勿封闭冰水管路循环,不得与其它管路共享。
Do not block the circulation of ice water pipeline and not share with other pipelines.
7、 冷却水塔可加杀藻剂和除垢剂,防防止青苔和水垢。
Algicide and cleaner can be added to the cooling water tower.
8、 冰水系统每隔三个月更换新水一次,若无法更换请加除锈剂。
Change the water of ice water system every 3 months. If not possible, please add rust remover.
9、 若为气冷式请定期清洗过滤网。
Clean the filter regularly if the chiller is air-cooling.
10、 本机使用R-22冷媒(CHCIF),请勿私自添加冷媒。
This machine uses R-22 cooling medium (CHCIF), please DONOT add
the medium by yourself.
11、 故障产生请依故障指示灯检查系统,如无法排除故障,请来电联系。
Follow the indicator light to check the system if malfunction occurs. If not able to solve, please call us.
※ 附注:冷凝器管路的清洗方法
※ Annotations: Cleaning method of condenser pipeline
(1).切断电源开关。
Cut the power supply.
(2).关闭冷却水进出口球阀。
Turn off the ball valve of cooling water inlet and outlet.
(3).拆下冷冻机前面板。
Dismantle the front panel of the chiller.
(4).将固定螺丝拆开,卸下圆形盖板,可见铜管。请使用铜刷来回清通即可。
Take the fixed screw apart and dismantle the round cover board to see the copper pipe. Please clean with a copper brush back and forth to make it through.
※ 请勿弄破橡胶垫片、保温棉,不得使用铁刷,以免刮伤铜管。
※ Please don’t break the rubber washer and heat preservation cotton, not use iron brush in case it will scratch the pipe.
※ 若无法清通,请以除垢剂清洗。如有不明之处,请来电,我司将有专员为您服务。
※ If not possible to clear it, please use cleaner. Any question, please call us and we have special person for you.
关键词:
① 凡本网注明"来源:易推广"的所有作品,版权均属于易推广,未经本网授权不得转载、摘编或利用其它方式使用。已获本网授权的作品,应在授权范围内
使用,并注明"来源:易推广"。违者本网将追究相关法律责任。② 本信息由注册会员:苏州奥天诚机械有限公司 发布并且负责版权等法律责任。
易推广客服微信